Refer to these sections for details:

Supported Series

Siemens LOGO! 0BA7,0BA8

Websitehttp://www.siemens.com/entry/cc/en/

PLC Connection Settings

ParametersRecommendedOptionsNotes
PLC TypeSiemens LOGO (Ethernet)
PLC InterfaceEthernet

Port #102

PLC Station #11 ~ 99
Local TSAP
1000
Must be greater than 1000
Local TSAP2100
Range: 2000~2700

LoopEdge DeviceHub Configuration

To configure DeviceHub for this Siemens Logo Ethernet PLC:

  1. DeviceHub > Add Device
    Type: Siemens
    Driver: Siemens Logo Ethernet



  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

DeviceType

Format

Range

Description

B

I

DD

1 ~ 64

Read Only
BQDD

1 ~ 64


BMDDD1 ~ 112
BNIDDD1 ~ 128
BNQDDD1 ~ 128
BVDDDDo0 ~ 14697VW_Bit
WAIDD1 ~ 16
WAQDD1 ~ 16
WAMDD1 ~ 64
WNAIDD1 ~ 64
WNAQDD1 ~ 32
WVBDDDD0 ~ 1469
WVWDDDD0 ~ 1468
WVDDDDD0 ~ 1466
WRTCD1 ~ 7