Refer to these sections for details:

Supported Series

Mitsubishi A2A, A2U, A2AS, A2USH

Website: http://www.mitsubishi-automation.com/

PLC Connection Settings

ParametersRecommendedOptionsNotes
PLC TypeMitsubishi A2A/A2U/A2AS/A2USH
PLC InterfaceRS232

Baud Rate9600

Data Bits8

ParityOdd

Stop Bits1

PLC Station #0

Parameter 100 ~ 8File register (0~8) K
Parameter 200 ~ 1Set A2A and A2USH to 1

LoopEdge DeviceHub Configuration

To configure DeviceHub for this Mitsubishi A2SH PLC:

  1. DeviceHub > Add Device
    Type: Mitsubishi
    Driver: Mitsubishi A2SH serial



  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

Device Type

Format

Range

Memo

B

X

HHHH

0 ~ 270f

Input Relay

BYHHHH0 ~ 270fOutput Relay
BMDDDD0 ~ 9999Auxiliary Relay
BBHHHH0 ~ ffff
BFDDDDD0 ~ 65535
WTVDDD0 ~ 255Timer Memory
WCVDDD0 ~ 255Counter Memory
WDDDDD0 ~ 9999Data Register
WWHHHH0 ~ ffff
WRDDDDD0 ~ 65535
  • No labels