Page tree
Skip to end of metadata
Go to start of metadata

Refer to these sections for details:

Supported Series

Panasonic FP/KW series (FP-X, FP-XH, FP-Σ, FP0, FP1, FP2, FP2SH, FP10SH)

Websitehttp://pewa.panasonic.com/

PLC Connection Settings

ParametersRecommendedOptionsNotes
PLC TypePanasonic FP/KW

PLC InterfaceRS232RS232/RS485
Baud Rate96009600, 19200, 38400
Data Bits87 or 8
ParityOddNone, Even, Odd
Stop Bits11 or 2
PLC Station #11 - 32Match the PLC port setting

LoopEdge DeviceHub Configuration

To configure DeviceHub for this Panasonic FP/KW PLC:

  1. DeviceHub > Add Device
    Type: Panasonic
    Driver: Panasonic FP Serial



  2. Enter details specific to your environment and click Add Device.

Device Addresses


Bit/Word

Device Type

Format

Range

Description

B

X

DDDDh

0 - 999915

Input

BYDDDDh0 - 999915Output
BRDDDDh0 - 999915Internal Relay
BLDDDD0 - 9999Link Relay
BL_BitDDDDh0 - 999915
BTDDDD0 - 9999Timer
BCDDDD0 - 9999Counter
WSVDDDD0 - 9999Timer or Counter Set Value
WEVDDDDD0 - 65535Timer or Counter Elapsed Value
WDTDDDDD0 - 262143Data Register
WLDDDDD0 - 8447Link Register
WWXDDDD0 - 9999Read-only Input
WWYDDDD0 - 9999Output
WWRDDDD0 - 9999Internal Relay
WWLDDDD0 - 9999Link Register
WFLDDDDD0 - 99999File Register
  • No labels