Refer to these sections for details:

Supported Series

Koyo Click PLC series

WebsiteAutomation Direct

PLC Connection Settings

ParametersRecommendedOptionsNotes
PLC TypeKoyo Click
PLC InterfaceRS232

Baud Rate384001200 ~ 115200
Data Bits8

ParityOddNone, Odd, Even
Stop Bits11, 2
PLC Station #11 ~ 247
Turnaround Delay55 ~ 10Set to 10 for PLC firmware version 2.1 or higher

LoopEdge DeviceHub Configuration

To configure DeviceHub for this Koyo Click PLC:

  1. DeviceHub > Add Device
    Type: Koyo
    Driver: Koyo Click



  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

Device Type

Format

Range

Description

B

X

Ddd

001 ~ 816

Input Status (Read Only)

B

Y

Ddd

001 ~ 816

Output Status

B

C

DDDD

1 ~ 2000

Control Bit

B

T

DDD

1 ~ 500

Timer Status (Read Only)

B

CT

DDD

1 ~ 250

Counter Status (Read Only)

B

SC

DDDD

1 ~ 1000

System Control Bit (Read Only)

W

DS

DDDD

1 ~ 4500

Data Registers

W

DD

DDDD

1 ~ 1000

Data Registers (Double Word)

W

DH

DDD

1 ~ 500

Data Registers

W

DF

DDD

1 ~ 500

Data Registers (Double Word)

W

XD

D

0 ~ 8

Input Status Registers (Read Only)

W

YD

D

0 ~ 8

Output Status Registers

W

TD

DDD

1 ~ 500

Timer Current Values (Read Only)

W

CTD

DDD

1 ~ 250

Counter Current Values (Double Word/Read Only)

W

SD

DDDD

1 ~ 1000

System Data Registers (Read Only)

W

TXT

DDDD

1 ~ 1000

Text Data Register