Refer to these sections for details:

Websitehttp://www.deltadriver.com

PLC Connection Settings

ParametersRecommendedOptionsNotes
PLC TypeDELTA DVPEN01-SL (Ethernet)
PLC Interface
Ethernet

Port #
502

PLC station #
0

LoopEdge DeviceHub Configuration

To configure DeviceHub for this Delta PLC:

  1. DeviceHub > Add Device
    Type: Delta PLC
    Driver: Delta SVP



  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

Device Type

Format

Range

Memo

B

C_Bit

DDD

0 ~ 255


BMDDDD0 ~ 4095
BSDDDD0 ~ 1023
BT_BitDDD0 ~ 255
BXOOO0 ~ 571
BYOOO0 ~ 571
WCDDD0 ~ 199
DWC_32BitDDD200 ~ 255
WDDDDDD0 ~ 11999
WTDDD0 ~ 255