Skip to end of metadata
Go to start of metadata

Refer to these sections for details:

Supported Series

Rockwell Automation Allen-Bradley PLC5 Ethernet.

Websitehttp://ab.rockwellautomation.com/

PLC Connection Settings

ParametersRecommendedOptions
PLC TypeRockwell PLC5 Ethernet
PLC InterfaceEthernet


Port #2222
PLC Station #11 ~ 31

LoopEdge DeviceHub Configuration

To configure DeviceHub for this PLC5 Ethernet PLC:

  1. DeviceHub > Device
    Type: Allen-Bradley
    DriverAB PLC5 Ethernet



  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

Device Type

Format

Range

Description

B

I

DDDdd

0 ~ 25515

Input (I)

B

O

DDDdd

0 ~ 25515

Output (O)

WSDDD

0 ~ 255

Status (S)

B

B3

DDDdd

0 ~ 25515

Bit data file (B3)

WT4.ACCDDD0 ~ 255
WT4.PREDDD0 ~ 255
WC5.ACCDDD0 ~ 255
WC5.PREDDD0 ~ 255
WR6DDD0 ~ 255
WR6.POSDDD0 ~ 255
WR6.LENDDD0 ~ 255
WN7DDD

0 ~ 255

Integer data file (N7)
WF8DDD

0 ~ 255

Floating point data file (F8)