Skip to end of metadata
Go to start of metadata

Refer to these sections for details:

Supported Series

Koyo Ethernet series (DirectLogic, H0-ECOM100, H2-ECOM100)

WebsiteAutomation Direct

PLC Connection Settings

ParametersRecommendedOptionsNotes
PLC TypeKoyo Ethernet
PLC InterfaceEthernet
UDP/IP
Port #28784

PLC Station #optional0

LoopEdge DeviceHub Configuration

To configure DeviceHub for this Koyo Ethernet PLC:

  1. DeviceHub > Add Device
    Type: Koyo
    Driver: Koyo Ethernet



  2. Enter details specific to your environment and click Add Device.

Device Addresses

Bit/Word

Device Type

Format

Range

Description

WCCM_31HHHH1 ~ 17056

V

WCCM_32HHH1 ~ 512

GX, X, SP

WCCM_33HHH1 ~ 832

GY,Y,C,S,T,CT

WVOOOOO0 ~ 17055V-memory

B

GX

OOOO

0 ~ 2047

Global I/O

B

X

OOOO

0 ~ 1023

Real Word Inputs

B

SP

OOOO

0 ~ 1023

Special Purpose Relays

B

GY

OOOO

0 ~ 2047

More Global I/O

B

Y

OOOO

0 ~ 1023

Real Word Outputs

B

C

OOOO

0 ~ 2047

Control Relays

B

S

OOOO

0 ~ 1023

Stage Status Bits

B

T

OOO

0 ~ 255

Timer Status Bits

B

CT

OOO

0 ~ 255

Counter Status Bits

  • No labels